The program protection methods for S7-1500 and S7-300/400 are not exactly the same 1. Read protection In the hardware configuration, open PLC Properties - Protection to set access permissions as needed. When selecting three protection levels other than "full access permission (no protection)", an access password needs to be set. Protection level: No protection, write protection, read-write protection, fully protected (password required for upper computer communication) 2. Protection of proprietary technology for program blocks The 1500CPU program blocks, including OB, FC, and FB, all support encryption functionality. DB also supports encryption function. After encryption, the attribute is read-only, and variables can be seen, but they cannot be added or deleted. Right click on the program block that needs to be protected, click on proprietary technology protec...
1、 Module Introduction CB1241RS485 allows the S71200 CPU to connect to other Modbus devices through this module, achieving the communication function of the S71200 Modbus RTU master station. The CB1241 RS485 module also supports communication connections such as USS and point-to-point PtP. The appearance of this module is shown in the following figure. The wiring terminals and connections for the CB1241 RS485 module are as follows: 2、 Configuration Introduction This example introduces the installation of CB1241RS485 module with two CT Uni SP drivers on S71200 CPU1215DC/DC V4.0 CPU. 1. Open TIA V13 software, create a new project, specify the project name and storage path. Click on the 'Left Explorer Window' Select 'Add New Device' in the 'Add CPU Type' section. In this example, select the S71200 1215 DC/DC C...