Common parameter settings for Emerson EV2000 series frequency converters
function code |
name |
Setting Range |
Minimum Unit |
Factory settings |
change |
F000 |
Frequency given channel selection |
0: Given a number of 1, adjust the ∧ and ∨ on the control panel 2: Number given 3, serial port given |
1 |
0 |
1 |
F002 |
Given the operating frequency number |
Lower limit frequency (F013)~upper limit frequency (F012) |
0.01Hz |
50Hz |
○ |
F004 |
Setting the direction of operation |
0: Forward rotation 1: Reverse rotation |
1 |
0 |
○ |
F005 |
Maximum Output Frequency |
Max (50.00, upper frequency limit)~650.0Hz |
0.01Hz |
50.00Hz |
× |
F006 |
Basic operating frequency |
1.00~650.0Hz |
0.01Hz |
50.00Hz |
× |
F008 |
Model selection |
0: G type (constant torque load model) 1: P-type (fan, pump type models) |
1 |
0 |
1 |
F009 |
Torque boost |
0.0 (automatic) 0.1%~30.0% |
0.1% |
0.0 |
0 |
F010 |
acceleration time |
0.1~3600S |
0.1S |
20.0S |
50 |
F011 |
Deceleration Time |
0.1~3600S |
0.1S |
20.0S |
30 |
F729 |
Selection of Analog Output Range |
LED position: AO1 for convenient selection 0: 0~10V or 0~20mA 1: 2~10V or 4~20mA LED position: AO2 for convenient selection 0: 0~10V or 0~20mA 1: 2~10V or 4~20mA |
1 |
00 |
○ |
FF01 |
Local address |
0~126 127 is the broadcast address |
1 |
1 |
× |
FH00 |
Number of motors |
2~14 |
2 |
4 |
× |
FH01 |
Motor rated power |
0.4~999.9kW |
0.1kW |
Model determination |
90 |
FH02 |
Rated current of motor |
0.1~999.9A |
0.1A |
Model determination |
Rated current |
FL00 |
Selection of motor overload protection mode |
0: No action 1: Ordinary motor (with low-speed compensation) 2: Variable frequency motor (without low-speed compensation) |
1 |
1 |
1 |
FL01 |
Overload protection coefficient of motor |
20.0~110.0% |
0.1% |
100% |
110% |
FP01 |
Parameter write protection |
0: All parameters are allowed to be rewritten 1: Except for the set frequency (F002) and this function code, other function code parameters are prohibited from being rewritten 2: All modifications are prohibited except for this function code |
|
|
○ |
FP02 |
parameter initialization |
0: Parameter rewriting status 1: Clear records (FL14~FL19) 2: Restore factory settings (excluding FL13, F008, and FH00) |
1 |
0 |
2 |
1. First enter FP01 input 0; FP02 input 2 returns to factory settings;
2. Enter the value in red again according to the table;
3. Then FP01 inputs 2;