Common parameter settings for Emerson EV2000 series frequency converters

Author: zhddq
Published on: 2025-04-27
Category: Industry News

function code

name

Setting Range

Minimum Unit

Factory settings

change

F000

Frequency given channel selection

0: Given a number of 1, adjust the ∧ and ∨ on the control panel

2: Number given 3, serial port given

1

0

1

F002

Given the operating frequency number

Lower limit frequency (F013)~upper limit frequency (F012)

0.01Hz

50Hz

F004

Setting the direction of operation

0: Forward rotation 1: Reverse rotation

1

0

F005

Maximum Output Frequency

Max (50.00, upper frequency limit)~650.0Hz

0.01Hz

50.00Hz

×

F006

Basic operating frequency

1.00~650.0Hz

0.01Hz

50.00Hz

×

F008

Model selection

0: G type (constant torque load model)

1: P-type (fan, pump type models)

1

0

1

F009

Torque boost

0.0 (automatic)

0.1%~30.0%

0.1%

0.0

0

F010

acceleration time

0.1~3600S

0.1S

20.0S

50

F011

Deceleration Time

0.1~3600S

0.1S

20.0S

30

F729

Selection of Analog Output Range

LED position: AO1 for convenient selection

0: 0~10V or 0~20mA

1: 2~10V or 4~20mA

LED position: AO2 for convenient selection

0: 0~10V or 0~20mA

1: 2~10V or 4~20mA

1

00

FF01

Local address

0~126 127 is the broadcast address

1

1

×

FH00

Number of motors

2~14

2

4

×

FH01

Motor rated power

0.4~999.9kW

0.1kW

Model determination

90

FH02

Rated current of motor

0.1~999.9A

0.1A

Model determination

Rated current

FL00

Selection of motor overload protection mode

0: No action

1: Ordinary motor (with low-speed compensation)

2: Variable frequency motor (without low-speed compensation)

1

1

1

FL01

Overload protection coefficient of motor

20.0~110.0%

0.1%

100%

110%

FP01

Parameter write protection

0: All parameters are allowed to be rewritten

1: Except for the set frequency (F002) and this function code, other function code parameters are prohibited from being rewritten

2: All modifications are prohibited except for this function code

 

 

FP02

parameter initialization

0: Parameter rewriting status

1: Clear records (FL14~FL19)

2: Restore factory settings (excluding FL13, F008, and FH00)

1

0

2

1. First enter FP01 input 0; FP02 input 2 returns to factory settings;
2. Enter the value in red again according to the table;
3. Then FP01 inputs 2;